Customization: | Available |
---|---|
Application: | Power |
Phase: | Three |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
3 Phase Pole Mounted Low Frequency Distribution Transformer includes hermetically sealed, amorphous alloy, conservator type and on-load tap changer type, which is usually pole mounted or installed in distribution station for daily lighting and factory power whose LV output up to 0.4kV. Our distribution transformer rating is up to 2500kVA, and primary voltage up to 35kV. The corrugated tanks as thermal expansion and contraction component enable the transformer oil completely isolated with the atmosphere. Oil distribution transformer with primary voltage range of 6,10,10.5,11,20,22,24,33, 35,38.5kV can be manufactured according to customer requirements.
On Load Tap Changer (OLTC) is a device used in power transformers to change the ratio of the voltage by regulating the voltage of the main circuit by controlling the tap position. OLTC is used to improve the efficiency and reliability of power transformers. The OLTC consists of a number of taps that can be adjusted to change the voltage ratio, which is usually mounted on the outside of the transformer and is connected to the primary and secondary windings of the transformer through oil filled circuits. When the OLTC is switched on, the oil circuit is pressurized, and the tap position is adjusted to regulate the voltage. The OLTC oil transformer is an essential component in modern power generation and distribution systems. Its ability to regulate the output voltage and reduce harmonic distortion makes it a reliable and cost-effective solution for a wide range of applications.
Please check below quick links for other product types.
Main Characteristics:
1. Low Oil Consumption: The tap changer is designed to consume less oil compared to traditional transformer tap changers.
2. Higher Torque Capacity: The tap changer is capable of delivering a higher torque capacity, making it suitable for high voltage applications.
3. Reduced Energy Loss: The tap changer uses advanced technologies to reduce energy loss, resulting in significant cost savings for the end user.
4. Reduced Noise: The tap changer is designed to minimize noise, making it a suitable option for installations where noise levels need to be minimized.
5. Increased Safety: The tap changer is equipped with safety features such as automatic resetting of the breaker and protection against short circuits, making it safe for use in power systems.
6. Efficient Operation: The tap changer is designed for efficient operation, with advanced features such as thermal protection and overcurrent protection to ensure optimal performance.
7. High Durability: The tap changer is built to last, with rugged construction and advanced materials to ensure long-term reliability and durability.
8. Simplified Maintenance: The tap changer is designed for ease of maintenance, with a simple interface and advanced diagnostic capabilities to simplify maintenance and reduce downtime.
Advantages:
1. Easy Operation.
The LTC allows the operator to quickly and easily change the tap settings on the transformer without having to physically touch the transformer. This saves time and reduces the risk of accidents.
2. Improved Efficiency.
By changing the tap settings, the LTC allows the transformer to operate at its most efficient point. This means that less power is lost in the transformer and more power is transmitted to the load.
3. Reduced Maintenance.
By using an LTC, the maintenance required on the transformer is reduced. This is because the LTC is self-contained and does not require regular inspection and maintenance of the tap-changing mechanism.
4. Enhanced Safety.
The LTC reduces the risk of injury to personnel when changing the tap settings. The LTC can be operated remotely, which reduces the need for personnel to be physically present in the transformer enclosure.
Applications
1. Building Infrastructure and Industrial: Airports, hospitals, factories, shopping malls, hotels, commercial and residential towers.
2. Utility: Generation, transmission, distribution substations, water and waste water treatment plants.
3. Oil and Gas: Oil and gas plants, petrochemical plants and refineries.
Service environment:
1. Ambient temperature: Maximum +40ºC, Minimum -40ºC
2. Altitude: less than 1000 meters.
3. Seismic level: less than 3m/s2 at horizontal direction and less than 1.5m/s2 at vertical direction.
4. Installation environment: No obvious and heavy pollution, no explosive and corrosive gas and dust, with good air ventilation and no severe vibration and shock.
(Note: If the application environment is different from the above standard conditions, please contact for customized designs.)
11KV Series On Load Tap Changer Oil Immersed Distribution Transformer Performance Parameters | |||||||||||||
High Voltage:11(6,6.3,10.5,11)KV Connection Symbol:D,yn11 or Y,yn0 Rated Frequency:50Hz/60Hz Low Voltage:0.4(0.415,0.433)KV Tapping Range of HV:±4x2.5% Insulation Level:LI75 AC35/AC3 |
|||||||||||||
Rated power (KVA) |
Short-Circuit Impedance(%) | SZ18 (W) | SZ13 (W) | SZ11 (W) | No-Load Current (%) |
Sound pressure dB(A) |
Weight (kg) |
Overall Dimension(mm) | |||||
No-Load Loss | On-Load Loss | No-Load Loss | On-Load Loss | No-Load Loss | On-Load Loss | L | W | H | |||||
200 | 4.0 | 300 | 2090 | 340 | 2320 | 380 | 2900 | 1.0 | 58 | 980 | 1700 | 830 | 1180 |
250 | 350 | 2460 | 395 | 2740 | 440 | 3420 | 0.9 | 58 | 1130 | 1700 | 880 | 1230 | |
315 | 420 | 2950 | 475 | 3280 | 530 | 4100 | 0.9 | 60 | 1300 | 1790 | 930 | 1290 | |
400 | 520 | 3560 | 580 | 3960 | 640 | 4950 | 0.8 | 60 | 1480 | 1870 | 930 | 1340 | |
500 | 610 | 4250 | 680 | 4715 | 760 | 5890 | 0.8 | 62 | 1710 | 1900 | 1010 | 1370 | |
630 | 4.5 | 780 | 5225 | 860 | 5810 | 960 | 7260 | 0.6 | 62 | 1950 | 2000 | 1070 | 1470 |
800 | 900 | 6400 | 1010 | 7110 | 1120 | 8890 | 0.6 | 64 | 2080 | 2100 | 1100 | 1720 | |
1000 | 1090 | 7490 | 1220 | 8320 | 1360 | 10400 | 0.6 | 64 | 2180 | 2300 | 1120 | 1750 | |
1250 | 1260 | 8860 | 1400 | 9840 | 1560 | 12300 | 0.5 | 67 | 3150 | 2430 | 1190 | 1980 | |
1600 | 1540 | 10580 | 1720 | 11760 | 1920 | 14700 | 0.5 | 67 | 4220 | 2620 | 1260 | 2080 | |
2000 | 5.0 | 1805 | 13400 | 2040 | 14880 | 2270 | 18600 | 0.4 | 69 | 4600 | 2720 | 1300 | 2110 |
2500 | 2140 | 15550 | 2410 | 17280 | 2680 | 21600 | 0.4 | 69 | 5500 | 2820 | 1360 | 2170 | |
Note: The above parameters are only for designing and selecting reference, and the final parameters are subject to the actual product. |
Qinghao Electric Co., Ltd. (Hereinafter referred to as Qinghao Electric) is a reliable and specialized power transmission and distribution equipment manufacturer located in Wenzhou City, Zhejiang Province. We are focusing on transformer, substation, switchgear and other power related products' R&D and manufacture from 2010. Our products mainly include oil immersed transformer, dry-type transformer, amorphous alloy transformer, prefabricated substation, pad mounted substation, solar photovoltaic & wind power step-up substation, high and low voltage switchgear.
With more than 20years develop and production efforts, our products are sold to many countries all over the world. Now our products' technical performance has reached the advanced level in power industry, and our company has become a leading professional power distribution manufacturer not only in China but also in the world. With the concept of "world-class transformers, smart solutions", Qinghao Electric is devoting to provide high-quality power for customers.
Let us cooperate with a brighter future!
Q: Are you a Manufacturer, factory or Trading company?
A: Yes, we are engaging over 20years in the research and development, production and operation of distribution equipment (transformer, switchgear, substation, etc.).
Q: What's your warranty terms?
A: We offer 24 months warranty time.
Q: How long is the production time?
A: 25 to 45 days or depending on order requirements.
Q: What's your payment terms?
A: T/T, L/C or negotiation.
Q: How do you conduct quality control in your factory?
A: Qinghao transformers are manufactured in accordance with international standards and customer requirements with IEC, SGS, Intertek, CCC, CE and other international certifications. All transformers are 100% conducting routine test, type test and special test in accordance with IEC Standards and customer requests at the end of the manufacturing process to ensure every product is qualified.
Q: Do you have the products in stock?
A: Normally no, but we have raw material stock to shorten production lead time.
Q: How can I trust you?
A: Qinghao Electric has more than 20years manufacturing experience, and cooperated with many customers all over the world. We have many patent certificates, CE certificate, KEMA certificate, ISO9001, ISO14000 certificate. We are the audited supplier of TUV and Made-In-China.
Q: What should provide to make custom transformer?
A: Technical drawing and specification documents are the best, or you can list key parameters for designing.
Q: Could I have your catalog and price list?
A: Price may change based on material market. Welcome to contact for accurate price via Made-in-China or company official website.